# NUT master upsmon.conf — UPS-connected host (e.g. 10.0.30.100) # Place at /etc/nut/upsmon.conf on the NUT master host. # Replace before deploying. # # Master mode: monitors the local UPS directly via upsd. # Uses upssched as NOTIFYCMD for timed FSD (30s on battery → force shutdown). # Master shuts down LAST — slaves receive FSD and shut down first. MONITOR apc@localhost 1 upsadmin upsmon master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h now" NOTIFYCMD /usr/sbin/upssched POLLFREQ 5 POLLFREQALERT 5 HOSTSYNC 15 DEADTIME 15 POWERDOWNFLAG "/etc/killpower" OFFDURATION 30 RBWARNTIME 43200 NOCOMMWARNTIME 300 FINALDELAY 5 NOTIFYFLAG ONLINE SYSLOG+WALL NOTIFYFLAG ONBATT SYSLOG+WALL NOTIFYFLAG LOWBATT SYSLOG+WALL NOTIFYFLAG FSD SYSLOG+WALL NOTIFYFLAG SHUTDOWN SYSLOG+WALL NOTIFYFLAG COMMOK SYSLOG NOTIFYFLAG COMMBAD SYSLOG+WALL