title: "EMHASS Kaskaden-Automations-Architektur"
category: reference
tags: [emhass, battery, cascade, homeassistant, byd, marstek]
created: "2026-10-02"
modified: "2026-10-08"
---
# EMHASS Kaskaden-Automations-Architektur
> Steuerung der dualen Batterie-Systems (BYD 11kWh + Marstek 5kWh) via EMHASS Optimizer + HA Kaskaden-Automation.
## Architektur-Übersicht
```
EMHASS (LP Solver) → sensor.smart_battery_target
↓
┌───────────────────┴──────────────────┐
│ Kaskaden-Automation (jede 2 Min) │
├───────────────────────────────────────┤
│ BYD/SMA: 803 Auto (default) │
│ 802 Manual (bei target≤0) │
│ Marstek: force_mode via │
│ sensor.marstek_target_power │
│ (= smart_target − BYD_actual)│
└───────────────────────────────────────┘
```
## EMHASS Configuration (12,32 kWh Virtual Battery)
> **Korrigiert 03.11.2026:** Kapazität war mit 16000 Wh angesetzt (Annahme BYD 11 kWh),
> real nutzbar sind 7,2 kWh (SMA SBS, aus 10 T Lade-/Entladehistorie gemessen) + 5,12 kWh
> (Marstek) = **12320 Wh**. `sensor.total_soc` rechnet seit dem Fix mit demselben Nenner,
> sonst wäre die SOC-Kurve inkonsistent zur Modellkapazität.
| Parameter | Value | Hinweis |
|-----------|-------|---------|
| `battery_nominal_energy_capacity` | 12320 | SMA 7,2 kWh nutzbar + Marstek 5,12 kWh |
| `battery_charge_power_max` | 6700 | 4200 (BYD) + 2500 (Marstek) |
| `battery_discharge_power_max` | 6700 | dto. |
| `battery_charge_efficiency` | 0.9 | Konservativ, gemischt |
| `battery_discharge_efficiency` | 0.9 | dto. |
| `battery_target_state_of_charge` | 0.15 | 15% Reserve (geändert von 0.30 am 2026-10-02) |
| `battery_soc_deficit_cost` | 0.5 | Strafe für Unterschreitung |
| `battery_minimum_state_of_charge` | 0.1 | 10% Hard Floor |
| `battery_maximum_state_of_charge` | 1.0 | 100% |
| `set_battery_dynamic` | True | Dynamische Peeling erlaubt |
| `set_use_battery` | True | Batterie aktiv |
| `sensor_battery_state_of_charge` | `sensor.total_soc` | Gewichteter Gesamt-SoC |
| `sensor_power_battery` | `sensor.batteries_power_out_total` | Entladeleistung |
| `use_websocket` | True | |
## ⚠️ Known Pitfall: set-config Full Overwrite
`POST /set-config` ersetzt die **gesamte** Konfiguration, nicht nur gesendete Felder.
Nicht angegebene Parameter fallen auf Defaults zurück (capacity→5000, power→1000, etc.).
**Regel:** Immer ALLE Parameter zusammen senden. Nach jedem Write mit `GET /get-config` verifizieren.
Siehe Solution Doc: `docs/solutions/integrations/2026-10-02-emhass-set-config-overwrite-pitfall.md`
## Kaskaden-Automation
**Automation ID:** `1774430238377` (ON)
**Schedule:** Alle 2 Minuten
**File:** `/mnt/data/supervisor/homeassistant/automations.yaml`
### BYD/SMA Steuerung
| EMHASS target | PV | BYD Modus | Bedeutung |
|--------------|-----|-----------|-----------|
| `> 0` (Entladung) | egal | **803 Auto** | BYD self-managed, Marstek kriegt Rest |
| `≤ 0` (Hold/Ladung) | `< 100W` | **802 Manual** | BYD hält/zwingt Ladung, EVCC hold |
| `< 0` (Ladung) | `≥ 100W` | **803 Auto** | PV reicht, BYD lädt selbst |
- BYD läuft permanent in Auto/Normal — nur bei EMHASS-Hold/Zwangsladung auf 802
- Modbus Register: 44425 (Mode), 44427 (Power)
- BYD IP: `10.0.50.202:502`
### Marstek Steuerung
- `sensor.marstek_target_power` = `smart_battery_target − actual_BYD_discharge + actual_BYD_charge`
- Cap: ±2500W
- Force modes: `charge`, `discharge`, `standby`
- Writable entities: `select.marstek_venus_modbus_force_mode`,
`number.marstek_venus_modbus_ladeleistung_einstellen`,
`number.marstek_venus_modbus_entladeleistung_einstellen`
- Marstek IP: `10.0.50.113`
### Gelöste Bugs
1. **Double-Counting (behoben 2026-10-01):** `sensor.sma_target_power` nahm volle EMHASS-Target,
ließ Marstek 0W. Fix: `sma_target_power` gelöscht, `marstek_target_power` nutzt jetzt
echte BYD-Werte (discharge - charge) statt Forecast-Split.
2. **Overnight Hold Too High (behoben 2026-10-02):** EMHASS hielt bei 65% weil
`target_state_of_charge=0.30`. Geändert auf 0.15.
3. **BYD ignoriert Hold (behoben 2026-10-02):** 802-Bedingung war `target < 0`,
jetzt `target <= 0` (Hold bei target=0 eingeschlossen).
## Template Sensoren (configuration.yaml)
- `sensor.smart_battery_target` — EMHASS p_batt_forecast, gerundet
- `sensor.marstek_target_power` — Plan A: smart_target − actual_BYD_net_discharge
- Guards: SoC-Checks, ±2500W cap
- `sensor.sma_target_power` — **ENTFERNT** (war Double-Counting Source)
## Cron Jobs
| Job ID | Schedule | Typ | Funktion |
|--------|----------|-----|----------|
| `a32005d62226` | every 15m | no_agent script | Ruft EMHASS Optimization auf, published Plan zu HA |
| `d046e808f543` | */15m | LLM-Agent (silent-on-healthy) | Shadow-Dual-Solve A/B + Ledger |
| `19aef2351273` | hourly :35 | no_agent script | Shadow-Staleness-Watchdog (>45 min -> Alert) |
Runner: `/home/debian/.hermes/scripts/emhass-optimizer-runner.sh`
Optimizer: `/home/debian/scripts/emhass_optimizer.py`
Shadow: `/home/debian/scripts/emhass_optimizer_v2.py --shadow` - Ledger `~/shadow_phase2/ledger.jsonl` - Report `~/scripts/report_phase2.py`
## Shadow Phase-2 (live seit 2026-10-08)
Dual-Solve-Validierung (A=Standard, B=grid-charge erlaubt) auf IDENTISCHEN
Inputs; Incumbent unangetastet. Bewiesene CSV-Gesetze: `+P`=Entladung,
`P_grid` signed net import (**Export NEGATIV**), Deferrable-Spalten =
Phantom-Last (+12 kWh Summeninvarianz, KEINE Consumer) ->
**produktiv entfernt 2026-10-08** (`number_of_deferrable_loads: 2->0`,
Direct-File-Edit + Addon-Restart im :50-Fenster, Backup
`config.json.hermesbak-20261008`; Beweis: Incumbent-CSV faellt auf 17
Spalten). Auswertung: `python3 ~/scripts/report_phase2.py`.
## Deaktivierte Komponenten
| Component | Status | Grund |
|-----------|--------|-------|
| Tibber Smart Charging Bridge | OFF | EMHASS ist sole optimizer |
| Marstek Kaskaden-Steuerung (Modbus) | OFF | Alte PV-only Kaskade, ersetzt durch EMHASS-Kaskade |
## Hardware Referenz
| Device | IP | Capacity | Max Power | Interface |
|--------|----|----------|-----------|-----------|
| BYD/SMA SBS | 10.0.50.202:502 | 11 kWh | 4.2 kW | Modbus 44425/44427 |
| Marstek Venus E | 10.0.50.113 | 5 kWh | 2.5 kW | HA Entities (Modbus) |
| SMA SB #1 | 10.0.50.201:502 | — | — | PV Wechselrichter |
| SMA SB #2 | 10.0.50.203:502 | — | — | PV Wechselrichter |
| Hoymiles | 10.0.40.55 | — | — | OpenDTU |
## Known Issues (2026-10-11)
1. **TZ-Bug in v2 build_pv_series — GEFIXT 11.10. 18:29**: `norm_key()` erzeugt Berlin-Wallclock-Keys,
Zurückparsen war als `tzinfo=timezone.utc` → +2h-Versatz im gesamten PV-Plan. Fix deployed:
`stamps = [datetime.strptime(k, "%Y%m%d%H%M").replace(tzinfo=BERLIN) for k in keys]`.
Backup: `emhass_optimizer_v2.py.bak-20261011-tzfix`. Live-Tick 18:28: korrekte Sunset-Kurve.
2. **Solcast-Kontamination (GEFIXT 11.10.)**: Demo-Site "Ogdak Netherlands" trug ~9,6 kWh/Tag
Phantom-PV bei; via Options-Flow `exclude_sites=["59c8-caae-52f5-1686"]` entfernt.
Optimizer-Tick danach: PV-Summe 59,0→36,3 kWh/24h, Peak 10,0→5,7 kW.
3. **Reload-Race-Crash (GEHÄRTET 11.10. 18:47)**: Solcast-Options-Reload → Sensoren ~16 s
`unavailable` → 18:43-Tick crashte. Fix: `collect_solcast_pools()` 3×10s-Retry, loud.
4. Solcast läuft mit EINER gemittelten Site ("Schön Rohr", 16 kW, -132,6°/19°); seit 11.10.
kalibriert via `auto_dampen=True` + `get_actuals=True` + `sensor.pv_production` als
Generationsquelle (Validator-Kopplung: auto_dampen erfordert get_actuals).
## Zugriff
- EMHASS API: `http://10.0.30.10:5000`
- HA intern: `http://10.0.30.10:8123`
- HA extern: `https://homeassistant.familie-schoen.com`
- SSH: `ssh -i ~/.ssh/id_ed25519_proxmox -p 22222 root@10.0.30.10`
- HA Token: `/tmp/ha_token.txt`
- HA Config: `/mnt/data/supervisor/homeassistant/`
- Backups: `.bak.20261001_175804` (configuration.yaml + automations.yaml)
## Related
- [[systems/homeassistant]] — HA System Seite
- Solution Doc: `docs/solutions/integrations/2026-10-02-emhass-set-config-overwrite-pitfall.md`